Ok app,,, took several minutes to figure out there is a answer screen under calculate box, don't show up on HTC aria unless scroll down
16gauge for 15amp .... see why you have such a disclaimer
#14 should not be used for a 20 amp circuit. First calculation I performed gave me a bad result. What else is wrong?
You guys complaining about the 14awg wire rating should read the NEC, #14 IS good for 20 amps just as 12 is good for 30 (excluding insulation type differences in this example). The problem is that the NEC only allows it to be placed on a 15amp breaker and 12 on a 20amp. So technically the app is correct, the dev would be wrong if he stated otherwise. Just throwing it out there...
My temperature correction choice was accidently changed from Celsius to Fahrenheit and that gave me embarrassing results.